Online Shop:

Search us:

Time Relay MTR17-C07-U240-208

  • 7 functions, version C
  • 7 time rangers 1s … 100h
  • Universal power supply of 12…240V AC/DC
  • 2NO/NC 8A contact arrangement
  • Low power consumption – <2.5 VA or <2 W – high energy efficiency
  • Installation design DIN 35mm
  • 17.5mm width

Multifunction time relays are particularly accurate in reaching the time limit even over long periods of time. With the universal supply of 12…240V AC/DC and different functions it is possible to find solutions even to the most challenging problems.
The brain chip of your application-specific miniature controller is the ideal solution for realizing custom control applications within minimum space at low-cost.

Time functions available in the MTR17-C07-U240-208 relay:

ON delay with STOP (TAS) – on applying the supply voltage U the R relay is in OFF position and the set interval T begins. After the interval T has lapsed, the output relay R switches ON and remains ON until supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is suspended until the contact is open again.
ON for the set interval with STOP (TBS) – on applying the supply voltage U the R relay is in ON position and the set interval T begins. After the interval T has lapsed, the output relay R switches OFF and remains OFF until supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is suspended until the contact is open again.
Symmetrical cyclical operation pause first with STOP (TCS) – applying the supply voltage U starts the cyclical operation – switching the output relay R OFF followed by switching ON for the interval T. The cyclical operation lasts until the supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is suspended until the contact is open again.
Symmetrical cyclical operation pulse first with STOP (TDS) – applying the supply voltage U starts the cyclical operation – switching the output relay R ON followed by switching OFF for the interval T. The cyclical operation lasts until the supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is suspended until the contact is open again.
ON delay with RESET (TAR) – on applying the supply voltage U the R relay is in OFF position and the set interval T begins. After the interval T has lapsed, the output relay R switches ON and remains ON until supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is stopped without the relay state change. Once the S contact is opened again the relay restarts.
ON for the set interval with RESET (TBR) – on applying the supply voltage U the R relay is in ON position and the set interval T begins. After the interval T has lapsed, the output relay R switches OFF and remains OFF until supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is stopped without the relay state change. Once the S contact is opened again the relay restarts.
Symmetrical cyclical operation pause first with RESET (TCR) – applying the supply voltage U starts the cyclical operation – switching the output relay R OFF followed by switching ON for the interval T. The cyclical operation lasts until the supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is stopped without the relay state change. Once the S contact is opened again the relay restarts.

Connections

Front Panel

Dimensions

Version MTR17-C07-U240-208
Output Circuit
Contact arrangement 2NO/NC
Rated switching current In AC1 – 8A/250V AC
DC1 – 8A/24V DC
Maximum continuous current 12A
Switching load range AC1 2 000VA
Rated/maximum contact voltage 250/400V AC
Contact resistance ≤ 100mΩ
Maximum switching frequency
600 cycles/h
Input Circuit
Supply voltage Un 12…240V AC/DC
Supply voltage range
0,8…1,1Un (9,6…264V)
Rated consumption AC: ≤ 2,5VA
DC: ≤ 2W
Rated frequency 47…63Hz
Minimum trigger level S-A2 (sensitivity) 0,7Un
Minimum control S pulse length AC: ≥ 90ms
DC: ≥ 45ms
S loadable yes
Rated surge voltage 1 000V
Insulation
Insulation rated voltage 250V AC
Rated surge voltage 4 000V (1,2/50μs)
Overvoltage category III
Pollution degree
2
Flammability PCB: V0, housing: HB
Dielectric strength input-output 4 000V AC
Dielectric strength open contact 1 000V AC
Dielectric strength between contacts 2 000V AC
General Data
Electrical life AC1 at 50% In ≥ 150 000
Mechanical life ≥ 30 000 000
Dimensions (L x W x H) 90 x 17,5 x 66mm
Weight 57g
Ambient temperature -20°C …. +55°C
Relative humidity 85%
IP rating IP20
Shock resistance 15g
Vibration resistance 0,35mm (10…55Hz)
Terminals max 2,5 mm²
Installation DIN rail 35mm
Time Module
Functions
TAS, TBS, TCS, TDS, TAR, TBR, TCR
Time ranges
1s, 10s, 1m, 10m, 1h, 10h, 100h
Timing adjustment smooth 0,1…1,0 x range
Setting accuracy
5%
Repeatability 0,5%
Recovery time ≤ 100ms

Order in e-shop

Order on allegro

Order by e-mail

e-sklep2 logo-allegro

 

MTR17-C07-U240-XXX Datasheet
Time Relay selection table
Declaration of conformity CE

Business partners

Join as. Dobry Czas sp. z o.o. invites to cooperation sales partners. Submit your proposal marketing@dobry-czas.pl

Welcome to the Dobry Czas e -shop

Welcome to our online store. The full portfolio of products. The certainty of the transaction.

read more

Monitoring relays ensures reliable system protection against demage.

It is used to secure loads (eg. motors) from the voltage unbalance, incorrect phase sequence or damage to the executive contactor’s contacts.

read more
Here you can subscribe to one of our NEWSLETTERS