Time Relay MTR17-A07-U240-208

  • 7 functions, version A
  • 7 time rangers 1s … 100h
  • Universal power supply of 12…240V AC/DC
  • 2NO/NC 8A contact arrangement
  • Low power consumption – <2.5 VA or <1.5 W – high energy efficiency
  • Installation design DIN 35mm
  • 17.5mm width

Multifunction time relays are particularly accurate in reaching the time limit even over long periods of time. With the universal supply of 12…240V AC/DC and different functions it is possible to find solutions even to the most challenging problems.
The brain chip of your application-specific miniature controller is the ideal solution for realizing custom control applications within minimum space at low-cost.

Time functions available in the MTR17-A07-U240-208 relay:

ON delay (TA) – on applying the supply voltage U the set interval T begins – off-delay of the output relay R. After the interval T has lapsed, the output relay R switches on and remains on until supply voltage U is interrupted.
ON for the set interval (TB) – on applying the supply voltage U immediately switches the output relay R on for the set interval T. After the interval T has lapsed, the output relay R
switches off.
Symmetrical cyclical operation pause first (TC) – applying the supply voltage U starts the cyclical operation from the T interval – switching the output relay R off followed by switching on the output relay R for the interval T. The cyclical operation lasts until the supply voltage U is interrupted.
Symmetrical cyclical operation pulse first (TD) – applying the supply voltage U starts the cyclical operation from switching on the output relay R for the set interval T. After the interval T has lapsed, the output relay R switches off for the interval T. The cyclical operation lasts until the supply voltage U is interrupted.
OFF delay with the control contact S (TF) – the input of the time relay is supplied with voltage U continuously. Closing of the control contact S immediately switches on the output relay R. Opening of the control contact S starts the set time of the delayed switching off of the output relay R. After the interval T has lapsed, the output relay R switches off. If the control contact S is closed during the interval T, the already measured time is reset, and the output relay R is switched on again. The OFF delay of the output relay R will start when the control contact S is opened again.
Single shot for the set interval triggered by closing of the control contact (TG) – single shot for the set interval triggered by closing of the control contact (TG) – The input of the time relay is supplied with voltage U continuously. Closing of the control contact S immediately switches the output relay R on for the set interval T. After the interval T has lapsed, the output relay R is switched off. In the course of the interval T, any opening of the control contact S does not affect the function to be performed. The output relay R may be switched on again for the set interval, after the interval T has lapsed, by closing the control contact S again.
ON for the set interval triggered with the control contact S (TI) -the input of the time relay is supplied with voltage U continuously. Closing of the control contact S does not start the interval T, and it does not change the position of the output relay R. Opening of the control contact S immediately switches on the output relay R for the set time. After the interval T has lapsed, the output relay R switches off. Opening and closing of the control contact S in the course of the interval T does not affect the function to be performed. The output relay R may be switched on again for the set interval with another closing and opening of the control contact S.
ON and OFF delay with the control contact (TJ) – – The input of the time relay is supplied with voltage U continuously. Closing of the control contact S starts the interval T – on-delay of the output relay R. After the interval T has lapsed, the output relay R switches on. Opening of the control contact S begins further measurement of the interval T – off-delay of the output relay R, and after the interval has lapsed, the output relay switches off. In case the time for which the control contact S is closed in the course of measurement of the on-delay of the output relay R is shorter than the set interval T, the output relay R will switch on after the set interval T, and the output relay R will remain in on position for the interval T. When the output relay R is in on position, closing of the control contact S does not affect the function to be performed.

Connections

Front Panel

Dimensions

Version MTR17-A07-U240-208
Output Circuit
Contact arrangement 2NO/NC
Rated switching current In AC1 – 8A/250V AC
DC1 – 8A/24V DC
Maximum continuous current 12A
Switching load range AC1 2 000VA
Rated/maximum contact voltage 250/400V AC
Contact resistance ≤ 100mΩ
Maximum switching frequency
600 cycles/h
Input Circuit
Supply voltage Un 12…240V AC/DC
Supply voltage range
0,8…1,1Un (9,6…264V)
Rated consumption AC: ≤ 2,5VA
DC: ≤ 2W
Rated frequency 47…63Hz
Minimum trigger level S-A2 (sensitivity) 0,7Un
Minimum control S pulse length AC: ≥ 90ms
DC: ≥ 45ms
S loadable yes
Rated surge voltage 1 000V
Insulation
Insulation rated voltage 250V AC
Rated surge voltage 4 000V (1,2/50μs)
Overvoltage category III
Pollution degree
2
Flammability PCB: V0, housing: HB
Dielectric strength input-output 4 000V AC
Dielectric strength open contact 1 000V AC
Dielectric strength between contacts 2 000V AC
General Data
Electrical life AC1 at 50% In ≥ 150 000
Mechanical life ≥ 30 000 000
Dimensions (L x W x H) 90 x 17,5 x 66mm
Weight 57g
Ambient temperature -20°C …. +55°C
Relative humidity 85%
IP rating IP20
Shock resistance 15g
Vibration resistance 0,35mm (10…55Hz)
Terminals max 2,5 mm²
Installation DIN rail 35mm
Time Module
Functions
TA, TB, TC, TD, TF, TG, TI, TJ
Time ranges
1s, 10s, 1m, 10m, 1h, 10h, 100h
Timing adjustment smooth 0,1…1,0 x range
Setting accuracy
5%
Repeatability 0,5%
Recovery time ≤ 100ms

Order in e-shop

Order on allegro

Order by e-mail

e-sklep2 logo-allegro

 

MTR17-A07-U240-XXX Datasheet
Time Relay selection table
Declaration of conformity CE

Business partners

Join as. Dobry Czas sp. z o.o. invites to cooperation sales partners. Submit your proposal marketing@dobry-czas.pl

Welcome to the Dobry Czas e -shop

Welcome to our online store. The full portfolio of products. The certainty of the transaction.

read more

Monitoring relays ensures reliable system protection against demage.

It is used to secure loads (eg. motors) from the voltage unbalance, incorrect phase sequence or damage to the executive contactor’s contacts.

read more
Here you can subscribe to one of our NEWSLETTERS