Time Relay MTR17-C07-U240-306
- 7 functions, version C
- 7 time rangers 1s … 100h
- Universal power supply of 12…240V AC/DC
- 3NO/NC 16A contact arrangement
- Low power consumption – <2.5 VA or <2 W – high energy efficiency
- Installation design DIN 35mm
- 17.5mm width
Multifunction time relays are particularly accurate in reaching the time limit even over long periods of time. With the universal supply of 12…240V AC/DC and different functions it is possible to find solutions even to the most challenging problems.
The brain chip of your application-specific miniature controller is the ideal solution for realizing custom control applications within minimum space at low-cost.
Time functions available in the MTR17-C07-U240-306 relay:
|
ON delay with STOP (TAS) – on applying the supply voltage U the R relay is in OFF position and the set interval T begins. After the interval T has lapsed, the output relay R switches ON and remains ON until supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is suspended until the contact is open again. |
|
ON for the set interval with STOP (TBS) – on applying the supply voltage U the R relay is in ON position and the set interval T begins. After the interval T has lapsed, the output relay R switches OFF and remains OFF until supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is suspended until the contact is open again. |
|
Symmetrical cyclical operation pause first with STOP (TCS) – applying the supply voltage U starts the cyclical operation – switching the output relay R OFF followed by switching ON for the interval T. The cyclical operation lasts until the supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is suspended until the contact is open again. |
|
Symmetrical cyclical operation pulse first with STOP (TDS) – applying the supply voltage U starts the cyclical operation – switching the output relay R ON followed by switching OFF for the interval T. The cyclical operation lasts until the supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is suspended until the contact is open again. |
|
ON delay with RESET (TAR) – on applying the supply voltage U the R relay is in OFF position and the set interval T begins. After the interval T has lapsed, the output relay R switches ON and remains ON until supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is stopped without the relay state change. Once the S contact is opened again the relay restarts. |
|
ON for the set interval with RESET (TBR) – on applying the supply voltage U the R relay is in ON position and the set interval T begins. After the interval T has lapsed, the output relay R switches OFF and remains OFF until supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is stopped without the relay state change. Once the S contact is opened again the relay restarts. |
|
Symmetrical cyclical operation pause first with RESET (TCR) – applying the supply voltage U starts the cyclical operation – switching the output relay R OFF followed by switching ON for the interval T. The cyclical operation lasts until the supply voltage U is interrupted. If the S contact is closed during the interval T, the timer is stopped without the relay state change. Once the S contact is opened again the relay restarts. |
Dimensions
Version |
MTR17-C07-U240-306 |
Output Circuit
|
|
Contact arrangement |
3NO/NC |
Rated switching current In |
AC1 – 6A/250V AC
DC1 – 6A/24V DC |
Maximum continuous current |
12A |
Switching load range AC1 |
1 500VA |
Rated/maximum contact voltage |
250/400V AC |
Contact resistance |
≤ 100mΩ |
Maximum switching frequency
|
600 cycles/h |
Input Circuit
|
|
Supply voltage Un |
12…240V AC/DC |
Supply voltage range
|
0,8…1,1Un (9,6…264V) |
Rated consumption |
AC: ≤ 2,5VA
DC: ≤ 2W |
Rated frequency |
47…63Hz |
Minimum trigger level S-A2 (sensitivity) |
0,7Un |
Minimum control S pulse length |
AC: ≥ 90ms
DC: ≥ 45ms |
S loadable |
yes |
Rated surge voltage |
1 000V |
Insulation
|
|
Insulation rated voltage |
250V AC |
Rated surge voltage |
4 000V (1,2/50μs) |
Overvoltage category |
III |
Pollution degree
|
2 |
Flammability |
PCB: V0, housing: HB |
Dielectric strength input-output |
4 000V AC |
Dielectric strength open contact |
1 000V AC |
Dielectric strength between contacts |
2 000V AC |
General Data
|
|
Electrical life AC1 at 50% In |
≥ 50 000 |
Mechanical life |
≥ 10 000 000 |
Dimensions (L x W x H) |
90 x 17,5 x 66mm |
Weight |
70g |
Ambient temperature |
-20°C …. +55°C |
Relative humidity |
85% |
IP rating |
IP20 |
Shock resistance |
15g |
Vibration resistance |
0,35mm (10…55Hz) |
Terminals |
max 2,5 mm² |
Installation |
DIN rail 35mm |
Time Module
|
|
Functions
|
TAS, TBS, TCS, TDS, TAR, TBR, TCR |
Time ranges
|
1s, 10s, 1m, 10m, 1h, 10h, 100h |
Timing adjustment |
smooth 0,1…1,0 x range |
Setting accuracy
|
5% |
Repeatability |
0,5% |
Recovery time |
≤ 100ms |
Order in e-shop
|
Order on allegro
|
|
|
|
|
|
MTR17-C07-U240-XXX Datasheet |
|
Time Relay selection table |
|
Declaration of conformity CE |