Main Parameters
Applications
Interface relays with dual 24V AC/DC or 230V AC power supply. Designed as installation module in 17,5mm width housing, equipped with one 1NO/NC 16A contact.
The state of the relay is indicated by green LED diode.
Applications: automatic systems in buildings – in cooperation with control timers, switches, control switches, electric systems, industrial automation and power engineering automation, switchgears of modular equipment.
An example application of the MIR17 relays is shown in the drawing below.
External connections |
Front panel |
Version | MIR17-002-M230-116 |
---|---|
Output circuit |
|
Contact arrangement | 1NO/NC |
Switching current In | AC1 – 16A/250V AC DC1 – 16A/24V DC |
Maximum continuous current | 12A |
Maximum switching load | 4 000VA |
Maximum switching voltage |
400V AC |
Contact resistance | ≤ 100mΩ |
Maximum operating frequency at rated load | 600 cycles/h |
Input Circuit |
|
Supply voltage Un | 24V AC/DC or 230V AC |
Operating range |
24V: 0,8…1,2 Un (19,2…28,8V) 230V: 0,8…1,1 Un (184…254V) |
Rated consumption | 24V DC: ≤ 0,5W 230V AC: ≤ 7,5VA |
Rated frequency AC | 47…63Hz |
Rated surge voltage | 1 000V |
Insulation |
|
Insulation rated voltage | 250V AC |
Rated surge voltage | 4 000V (1,2/50μs) |
Overvoltage category | III |
Insulation pollution degree | 2 |
Flammability | PCB: V0, housing: HB |
Dielectric strength input-output | 4 000 V AC |
Dielectric strength open contact | 1 000 V AC |
Dielectric strength between contacts | – |
General data |
|
Electrical life AC1 at 50% In |
≥ 150 000 |
Mechanical life | ≥ 30 000 000 |
Dimensions a x b x h | 90 x 17,5 x 66mm |
Weight | 47g |
Light indicator |
green LED |
Ambient temperature | -20°C …. +55°C |
Relative humidity | 85% |
IP rating | IP20 |
Shock resistance | 15g |
Vibration resistance | 0,35mm (10…55Hz) |
Cable size |
max 2,5 mm² |
Mounting | DIN Rail 35mm |
Order in e-shop |
Order on allegro |
Order by e-mail |
Join as. Dobry Czas sp. z o.o. invites to cooperation sales partners. Submit your proposal marketing@dobry-czas.pl
It is used to secure loads (eg. motors) from the voltage unbalance, incorrect phase sequence or damage to the executive contactor’s contacts.
read moreWelcome to our online store. The full portfolio of products. The certainty of the transaction.
read more