Online Shop:

Search us:

3 Phase Monitoring Relay MMR17-PPM-A230-108

  • MA function (asymmetry)
  • Contactor contacts control
  • Adjustable asymmetry threshold 30…70V
  • Fixed detection time 5s
  • Fixed recovery time 1.2s
  • 1NO/NC 8A contact arrangement
  • Installation design DIN 35mm
  • 17.5mm width

Time relay MMR17-PPM-A230-108 is designed to protect loads (inductive motors) against voltage asymmetry in 3 phase networks. If the assymetry voltage above the adjustable threshold 30…70V lasts longer than detection time 5s, the output relay is switched off. The relay can be recovered to normal operation if asymmetry drops below the threshold for at least 1.2s.

The relay also controls contactor contacts. If asymmetry is detected after the contactor, it means, that the contactor is broken. In this case the relay is permanently switched off. To restore normal operation power off – power on cycle is required.

If the contactor monitoring function is not needed, the V1, V2, V3 inputs can be left unconnected.

Time function available in the MMR17-PPM-A230-108 relay:

Functions – MA (asymmetry) – Asymmetry monitoring. As soon as the asymmetry exceeds the value at the Uas – regulator, the set interval of the tripping delay (DELAY) begins. After the interval has expired the output relay R switches into off-position (yellow LED not illuminated).

Connections with contactor control

Connections without contactor control

Front Panel

Dimensions

Version MMR17-PPM-A230-108
Output Circuit
Contact arrangement 1NO/NC
Rated switching current In AC1 – 8A/250V AC
DC1 – 8A/24V DC
Maximum continuous current 8A
Switching load range AC1 2 000VA
Rated/maximum contact voltage 250/400V AC
Contact resistance ≤ 100mΩ
Maximum switching frequency
600 cycles/h
Input Circuit
Supply voltage Un 3x 400/250V AC
Tolerance
0,8…1,1Un (184…253V)
Phase power supply of control circuit L1
Rated consumption ≤ 8VA
Rated frequency 47…63Hz
Rated surge voltage 1 000V
Insulation
Insulation rated voltage 400V AC
Rated surge voltage 4 000V (1,2/50μs)
Overvoltage category III
Pollution degree
2
Dielectric strength input-output 4 000V AC
Dielectric strength open contact 1 000V AC
Measuring circuit
Regulation asymmetry range Uasym
30…70V
Functions MA
Setting accuracy
≤ 5%
Repeatability ≤ 2%
Time Module
Time off delay
5s
Recovery time
1.2s
Reset time
≤ 500ms
Timing accuracy
20%
General data
Electrical life AC1 at 1000VA resistive load
≥ 150 000
Mechanical life
≥ 10 000 000
Dimensions (L x W x H)/Weight
90 x 17.5 x 66mm / 53g
Ambient temperature
-20…+55°C
Storage temperature -40…+70°C
IP rating IP20
Relative humidity
85%
Shock resistance 15g
Vibration Resistance 0.35mm (10…55Hz)
LED indicator 2 LED

Order in e-shop

Order on allegro

Order by e-mail

e-sklep2 logo-allegro

 

On request
Declaration of conformity CE

 

Business partners

Join as. Dobry Czas sp. z o.o. invites to cooperation sales partners. Submit your proposal marketing@dobry-czas.pl

Monitoring relays ensures reliable system protection against demage.

It is used to secure loads (eg. motors) from the voltage unbalance, incorrect phase sequence or damage to the executive contactor’s contacts.

read more

Welcome to the Dobry Czas e -shop

Welcome to our online store. The full portfolio of products. The certainty of the transaction.

read more
Here you can subscribe to one of our NEWSLETTERS